Industrial pipeline blowers are widely used in industrial production. Because they can be connected to pipelines for coordinated operation, they can complete some special tasks. However, industrial pipeline blowers sometimes fail, and the difficulty of troubleshooting is still relatively high. In this article we will take a look at the fault solutions of industrial duct blowers in the future.
The blower is a necessity for dust removal and purification. However, in the later operation, the blower will always have problems of one kind or another. When the blower is abnormal, what if the problem is effectively solved? This article discusses the common occurrence of the blower. The problem.
Air volume is too small
Cause and solution
1
Reason: The system resistance is too large and the blower is improperly selected
Solution: re-evaluate the design of the system, re-selection
2
Reason: system air duct is leaking or blocked by debris
Solution: plugging or cleaning
3
Reason: Impeller steering error
Solution: Correct the steering: Swap the position of the two-phase power lines of the motor arbitrarily
4
Reason: The opening angle of the adjusting door is too small
Solution: adjust
5
Reason: The density of the conveying gas increases (the gas contains too many solid impurities or the gas temperature is too low, etc.)
Solution: Eliminate the cause of the increase in gas density
6
Reason: The V-belt slips and causes the speed to decrease
Solution: adjust the belt tension
7
Reason: The gap between the impeller and the air inlet is too large or the blades are seriously worn
Solution: repair, replace
Excessive air volume
Cause and solution
1
Reason: The system resistance is too small and the blower is improperly selected
Solution: increase the system resistance (such as properly blocking the air inlet, etc.) or reduce the blower speed
Motor overload, abnormal temperature rise
Cause and solution
1
Reason: The system resistance is small and the air volume is too large (centrifugal blower)
Solution: increase system resistance or reduce blower speed
2
Reason: The system resistance is large and the air volume is too small (axial blower)
Solution: reduce system resistance
3
Reason: The density of the conveying gas increases (the gas contains too many solid impurities or the gas temperature is lower than the rated operating temperature, etc.)
Solution: Eliminate the cause of the increase in gas density
4
Reason: The opening angle of the adjusting door is too small
Solution: adjust
5
Reason: V-belt is too tight
Solution: adjust the belt tension
6
Reason: The motor power is too small
Solution: replace the motor
7
Reason: Motor wiring error
Solution: Check the circuit
8
Reason: poor insulation, motor failure
Solution: Repair or replace
abnormal sound
Cause and solution
1
Reason: The bearing has cracks, scars or impurities mixed into the bearing
Solution: replace the bearing
2
Reason: Insufficient lubricating oil (bearing whistling accompanied by temperature rise)
Solution: Come on
3
Reason: The bearing lock nut is loose
Solution: Re-lock
4
Reason: Spindle wear
Solution: change the shaft
5
Reason: Shaft play
Solution: Find the cause and fix it
6
Reason: The impeller rubs against the air inlet or the casing
Solution: Repair, Adjust
7
Reason: The bolts connecting the impeller and the hub or the shaft head are loose
Solution: Tighten the bolts
8
Reason: The blower sucks in foreign objects
Solution: Clear
9
Reason: The opening angle of the adjusting door is too small
Solution: adjust
10
Reason: poor piping system, excessive wind speed
Solution: Retrofit the piping system
Abnormal bearing
Cause and solution
1
Reason: too much lubricating oil, too much grease filling (often accompanied by oil leakage)
Solution: remove the excess part
2
Reason: Insufficient lubricating grease or poor oil quality
Solution: add grease or replace with new grease
3
Reason: improper selection of lubricating grease, model does not meet the requirements
Solution: Clean the bearing and replace with qualified grease
4
Reason: The opening angle of the adjusting door is too small
Solution: adjust
5
Reason: bearing installation is too tight
Solution: Check and reinstall the bearing
6
Reason: bearing failure or fatigue wear
Solution: Check and replace the bearing
Vibration
Cause and solution
1
Reason: The impeller is unbalanced (rust, dust, dirt and other foreign objects adhere to the impeller)
Solution: clean the impeller
2
Reason: impeller deformation or serious wear
Solution: replace the impeller
3
Reason: Poor foundation design, or resonance caused by insufficient strength and rigidity of the foundation
Solution: Check the foundation condition, repair and reinforce properly
The anchor bolts are loose and locked
4
Reason: mechanical vibration caused by poor bearing installation or damage
Solution: Reinstall the bearing or replace it
5
Reason: motor vibration caused by motor failure
Solution: Repair or replace the motor
6
Reason: Spindle bending deformation or wear
Solution: change the shaft
7
Reason: improper installation of coupling or pulley
Solution: adjust and recalibrate
8
Reason: External vibration (such as pipeline vibration, etc.) is transmitted to the blower
Solution: The connection between the blower and the pipeline adopts a flexible flexible pipe, and a shock absorber is installed.
9
Reason: improper selection, causing the blower to work under unstable conditions (the blower surges and is accompanied by intermittent noise)
Solution: adjust the blower speed or re-selection
In summary, the troubleshooting of industrial pipeline blowers requires patience and meticulousness. Because the types of faults of industrial pipeline blowers are more complex, the difficulty of troubleshooting has also increased accordingly. Therefore, we should compare and analyze the faults according to the overall performance of the industrial pipeline blower, so as to effectively solve the fault.
Read recommendations:
A2 aroma diffuser.essential diffuser
Three differences between aroma diffuser and humidifier
How to reduce noise better for GXF axial flow blower.electric fan manufacture
NextThe process of installing and debugging the motor energy-saving EC fan
Popular recommendation
F07 Cooling Fan
2021-09-14A8 Flame Aroma Diffuser
2022-04-19J17 Air Humidifier
2021-09-14TS02
2022-02-17J9 usb humidifier
2021-09-14Exquisite and beautiful life, starting from a bottle of aromatherapy~aromatherapy diffuser
2022-06-07Can essential oils be applied directly to the body?
2022-04-07What should we know before we buy a soap dispenser?
2022-05-16Air purifier for the crowd
2022-03-14Can the aroma diffuser be used as a humidifier?aroma diffuser manufacture
2021-10-27Does the humidifier emit radiation
2024-09-28Is using a humidifier at home harmful to the body?
2024-09-09How long does a dehumidifier usually run per day?
2024-09-09Humidifier classification
2024-08-24Humidifiers nourish daily life
2024-08-17Common classification methods for humidifiers
2024-08-10How to dehumidify with a dehumidifier
2024-07-22Working process of dehumidifier
2024-07-22High pressure micro fog humidifier for air conditioning unit
2024-07-13What are the possible reasons why humidifiers do not produce fog
2024-07-08Contact the following for inquiries regarding our services and products.